HORIZONTAL SLIDING WINDOW (GD)
SERIES 1659 ALUMINUM
DSB ANNEALED GLASS
HARCO BUILDING PRODUCTS
1000 N. 3rd Street
P.O. Box 11115
Phoenix, AZ 85011
Phone: (602) 266-8500
Fax: (602) 266-8501
Sheet 1 of 3
Project No. UN
Date 12-1-99
Drawn by
Checked by
Sheet No. HS99-01
WINDOW HEIGHT
18 3/8" MAX
5" MAX
DSB ANNEALED GLASS
DSB ANNEALED GLASS
21 1/4" MAX
WINDOW WIDTH
20 1/2" MAX
5" MAX
FALSE MULLION (SURFACE APPLIED)
MAY BE USED
TYPICAL ELEVATION (GD)
NOTE:
1- SUB-FOOT SHALL BE PRESSURE-TREATED LUMBER 6'x6" x 12' MINIMUM. INSTALLATION SHALL BE AT LEAST 6' FROM ANY BUILDING PARTITION OR COLUMN.
2- FASTENERS ARE 1/4" DIAMETER x 12" LONG. AND MUST BE MADE OF STAINLESS STEEL OR HOT-DIP GALVANIZED STEEL. PROTECTION AGAINST CORROSION FOR STEEL FASTENERS IN CONTACT WITH ALUMINUM OR OTHER METALS NOT CONSIDERED COMPATIBLE SHALL BE PROVIDED.
PRODUCT RE-REVIEWED
ACCEPTANCE No. 21-013-99
REPORT NO. 21-013-99
HARCO BUILDING PRODUCTS
WATER-GLIDE PRODUCT ELEVATION DETAILS REQUIRED
APPROVED AS COMPLYING WITH THE
SOUTHERN BUILDING CODE
HARCO BUILDING PRODUCTS
1000 N. 3RD STREET
PHOENIX, ARIZONA 85011
JOSEPH PERNAKOSZ
PHOENIX, PE P 51535
3-22-99
COMPATIBLE ANCHORING
SERIES 1659
ALUMINUM HORIZONTAL SLIDING WINDOW (GD)
DESIGN LOAD CAPACITY
WINDOW DIMENSION
WIDTH HEIGHT
ANCHORS
DSB ANNEALED GLASS
1.54" SILL
EXT.
INT.
3.00" SILL
EXT.
INT.
NORMAL SIZES
36 1/2" 36" 3 55.3 140.0 70.0 160.0
36 1/2" 48" 3 55.3 140.0 70.0 160.0
36 1/2" 60" 4 55.3 113.3 70.0 115.3
36 1/2" 72" 5 55.3 95.1 70.0 96.1
36 1/2" 84" 6 55.3 82.7 70.0 82.7
36 1/2" 96" 3 55.3 113.3 70.0 115.3
36 1/2" 108" 4 55.3 77.8 70.0 72.8
36 1/2" 120" 5 55.3 59.6 70.0 59.6
STANDARD SIZES
48 1/2" 36" 3 55.3 80.7 70.0 80.7
48 1/2" 48" 4 53.4 53.4 53.4 53.4
48 1/2" 60" 5 53.3 37.1 37.1 37.1
48 1/2" 72" 6 55.3 28.8 28.8 28.8
48 1/2" 84" 3 55.3 70.0 70.0 70.0
48 1/2" 96" 4 55.3 48.3 70.0 56.9
48 1/2" 108" 5 55.3 140.0 70.0 140.0
48 1/2" 120" 2 55.3 140.0 70.0 140.0
60 1/2" 36" 3 55.3 111.2 70.0 111.2
60 1/2" 48" 4 55.3 70.0 70.0 81.1
60 1/2" 60" 5 55.3 140.0 70.0 140.0
60 1/2" 72" 2 55.3 121.1 70.0 121.1
60 1/2" 84" 3 55.3 81.6 81.6 81.6
60 1/2" 96" 4 55.3 64.8 64.8 64.8
60 1/2" 108" 5 55.3 54.1 54.1 54.1
60 1/2" 120" 3 55.3 85.5 70.0 85.5
72 1/2" 36" 4 55.3 83.5 83.5 83.5
72 1/2" 48" 5 48.6 48.6 48.6 48.6
72 1/2" 60" 3 55.3 85.2 85.2 85.2
72 1/2" 72" 4 55.3 66.7 66.7 66.7
72 1/2" 84" 5 55.3 54.7 54.7 54.7
72 1/2" 96" 3 55.3 37.7 37.7 37.7
BASED ON TCI-100-99 12-22-99
SOUTHERN BUILDING CODE
TEST LOADS - DESIGN PRESSURE +33.1 PSF
SUSTAINING PRESSURE -33.1 PSF
DESIGN LOADS - DESIGN PRESSURE +24.4 PSF
SUSTAINING PRESSURE -24.4 PSF
WIND LOADS 110 MPH
WIND EXPOSURE B
WIND IMPORTANCE FACTOR 1.0
27
Product Specification — Harco Building Products, Report No. 21-013-99 (1999)