27
HS98-047
SHEET 2 OF 3
DATE: 8-18-99
DWG NO: 1/2-1
SCALE: 1-1/2" = 1'-0"
PROJECT: HORIZONTAL SLIDING WINDOW (GD)
SERIES 1650 ALUMINUM
1/4" TEMPERED GLASS
PLANNED DEVELOPMENT
Structural Engineering
551 NW 2nd Ave #1118
Miami, FL 33136
Phone: (305) 374-3477
Fax: (305) 374-3477
Consulting Services
10000 Biscayne Blvd
Suite 100
North Miami, FL 33138
VERTICAL SECTION
ATTACHMENT TO WOOD
3/16" TAPCON 1 1/4" MIN. EMBEDMENT
FOR NUMBER OF ANCHORS AND MAX. SPACING REFER TO SHEET 1)
3/4" SILL
WINDOW HEIGHT
ATTACHMENT TO MASONRY VERTICAL
3/16" TAPCON 1 1/4" MIN. EMBEDMENT
FOR NUMBER OF ANCHORS AND MAX. SPACING REFER TO SHEET 1)
3/4" SILL
WINDOW WIDTH
VERTICAL SECTION WITH SILL RISER
ATTACHMENT TO WOOD
3/16" TAPCON 1 1/4" MIN. EMBEDMENT
FOR NUMBER OF ANCHORS AND MAX. SPACING REFER TO SHEET 1)
3" SILL RISER
3/4" SILL
WINDOW HEIGHT
HORIZONTAL SECTION
ATTACHMENT TO WOOD DETAIL
3/16" TAPCON 1 1/4" MIN. EMBEDMENT INTO MASONRY
FOR NUMBER OF ANCHORS AND MAX. SPACING REFER TO SHEET 1)
3/4" SILL 1 1/2" MIN. EMBEDMENT INTO WOOD
FOR NUMBER OF ANCHORS AND MAX. SPACING REFER TO SHEET 1)
WINDOW WIDTH
VERTICAL SECTION
ATTACHMENT TO MASONRY
3/16" TAPCON 1 1/4" MIN. EMBEDMENT INTO MASONRY
FOR NUMBER OF ANCHORS AND MAX. SPACING REFER TO SHEET 1)
3/4" SILL
WINDOW HEIGHT
GLAZING:
MATERIAL: 1/4" TEMPERED GLASS
METHOD:
USE 1/4" TEMPERED GLASS IN ALL LITES.
ALL VERTICAL EDGES OF GLASS MUST BE GROUNND AND POLISHED.
ALL HORIZONTAL EDGES OF GLASS MUST BE GROUNND.
USE NEOPRENE BEAD AND THERMOPASTIC AT EACH VERTICAL AND HORIZONTAL EDGE OF GLASS.
NOTE: GLASS NOT TO DAMAGE, SCRATCH, ABRADE, OR OTHERWISE WORST GLASS BY GLASS INSTALL.